Liz, all DuoTherm roof units have a freeze control device specifically mounted on the evaporator coils. The positioning of the control switch is crucial to proper operation. Have someone check for the proper positioning of the control switch and that it indeed measures no continuity when the ambient temperature is over 69-degrees. Pictured above is a diagram from the service manual to help you understand the location of this switch. It’s entirely possible the switch has come loose from its mounting or is faulty. This freeze control is a thermally-activated switch of sorts that closes once the temperature of the evaporator falls below 49-degrees F. Once closed, it will re-open when the temperature rises to between 61 and 69-degrees F. If it fails to open and the temperature is above 69-degrees, it needs to be replaced. A simple continuity test and temperature measurement should quickly reveal the status of your freeze control device.