I have an older Pace Arrow that has two roof air conditioning units. The front air conditioner will not run (fan or compressor) on shore power. When I start the generator the front unit will work as normal. Any suggestions? Lost for answers! B., (Aiken, SC)
Well Bruce, it’s apparent your motorhome is equipped with only a 30-amp shoreline service. Having a 30-amp limitation basically means that you can only operate one air conditioner at a time while connected to shore power. The reason for this is that, on your Pace Arrow, each air conditioner must be on it’s own, separate 20-amp breaker. So in order to operate all the other 120-volt AC accouterments, you’re limited to only one roof air at a time. It’s simply basic math.

50-amp coaches do not have this problem since there are 50-amps available on two separate legs of 120-volts. On those RVs, each air conditioner is connected through a different leg. Again, it’s all in the math.
If it is extremely important to operate both air conditioners at the same time, the only safe and code-compliant option is to install an aftermarket energy management system (EMS), which will automatically cycle each air conditioner, one at a time. Let me know if you cannot locate those “either/or” switches and we’ll dig a little further if necessary.